MODEL | EAB-110 | EAB-120 | EAB-140 | EAB-160 |
INPUT |
Phase | 1Ø | 1Ø or 3Ø |
Voltage | 100V - 240V±10% | 200V - 240V±10% | 1Ø / 3Ø3W: 200V - 240V±10% |
3Ø4W: 346V - 416V±10% |
Frequency | 47 - 63Hz |
Max. Current | 15 | 30 | 30 | 1Ø:45A |
3Ø3W:26A |
3Ø4W:15A |
Power Factor | 0.97 |
AC OUTPUT |
Max Power | 1000VA | 2000VA | 4000VA | 6000VA |
Max Current 1Ø (r.m.s)*1 | 0-150V | 9.2 A | 18.4 A | 36.8 A | 55.2 A |
0-300V | 4.6 A | 9.2 A | 18.4 A | 27.6A |
Inrush Current (peak) | 0-150V | 36.8A | 73.6A | 147.2A | 220.8A |
0-300V | 18.4A | 36.8A | 73.6A | 110.4A |
Phase | 1Ø, (Linking Option 1Ø3W or 3Ø4W Poly-Phase) |
Total Harmonic Distortion (THD) | <0.5% (Resistive Load) at 40.0 - 70.0Hz and output voltage within the 80 - 140Vac at |
Low Range or the 160 - 280Vac at High Range |
<1% (Resistive Load) at 70.1 - 500Hz and output voltage within the 80 - 140Vac at |
Low Range or the 160 - 280Vac at High Range |
<1% (Resistive Load) at 501 - 1000Hz and output voltage within the 100 - 140Vac |
at Low Range or the 160 - 280Vac at High Range |
Crest Factor | ≧3 |
Line Regulation | ± 0.1 V |
Load Regulation | ± (1% of output +1V) at Resistive Load |
Response Time | < 400 µsec |
SETTINGS |
Voltage | Range | 5 - 300V, 150 / 300V Auto Range |
Resolution | 0.1V |
Accuracy | ±(1% of setting + 2counts) | ±(1% of setting + 5counts) |
Frequency | Range | 40 - 1000Hz Full Range Adjust |
Resolution | 0.1Hz at 40.0 - 99.9Hz, 1Hz at 100 - 1000Hz |
Accuracy | ±0.03% of setting |
Starting & Ending | Range | 0-359∘ |
Phase Angle | Resolution | 1∘ |
| Accuracy | ±1∘(45 - 65HZ) |
DC OUTPUT |
Max Power | 1000W | 2000W | 4000W | 6000W |
Max Current | 0-210V | 4.8A | 9.6A | 19.2A | 28.8A |
0-420V | 2.4A | 4.8A | 9.6A | 14.4A |
Ripple & Noise (rms) | Range | L | < 500mV | < 700mV |
H | < 800mV | < 1100mV |
Ripple & Noise (p-p) | < 3.0Vp-p | < 4.0Vp-p |
SETTINGS |
Voltage | Range | 0 - 210V / 0 - 420V Selectable | 0-210V / 0-420V Selectable >5V |
Resolution | 0.1V |
Accuracy | ± (1% of setting + 2 counts) | ± (1% of setting + 5 counts) |
Current Hi Limit | Range | L | 0.01 - 4.80A | 0.01 - 9.60A | 0.10 - 19.20A | 0.10 - 28.80A |
(OC Fold=OFF) | H | 0.01 - 2.40A | 0.01 - 4.80A | 0.10 - 9.60A | 0.10 - 14.40A |
OC Fold Back | Resolution | 0.01 Amps |
(OC Fold = ON) | Accuracy | ± (2.0% of setting + 2counts) |
MEASUREMENT |
Voltage | Range | 0 - 210V / 0 - 420V | 0 - 210V / 0 - 420V Selectable >5V |
Resolution | 0.1 V |
Accuracy | ± (1% of reading + 2counts) | ± (1% of reading + 5counts) > 5 V |
Frequency | Range | 0.0 - 1000 Hz |
Resolution | 0.1 Hz |
Accuracy | ±0.1Hz (501 - 1000Hz Accuracy ± 0.2Hz) |
Current (AC & DC) | Range | L | 0.005 A - 1.200 A | 0.005 A - 2.400 A | - | - |
H | 1.00 A - 13.00 A | 2.00 A - 26.00 A | 0.05 A - 52.00 A | 0.05 A - 78.00 A |
Resolution | L | 0.001A | - | - |
H | 0.01A |
Accuracy | L | ± (1% of reading + 5counts) |
H | ± (1% of reading + 5 counts) |
Current Peak | Range | 0.0A - 38.0 A | 0.0 A - 76.0 A | 0.0 A - 152.0 A | 0.0 A - 228.0A |
Resolution | 0.1 A |
Accuracy | ± (1% of reading + 5 counts) |
Power (AC) | Range | L | 0.0 W - 120 W | 0.0 W - 240 W | - | - |
H | 100 W - 1300 W | 200 W - 2600 W | 0 W - 5200 W | 0 W - 7800 W |
Resolution | L | 0.1W | - | - |
H | 1W |
Accuracy | L | ± (2% of reading + 15counts ) at PF > 0.2 | - |
H | ± (2% of reading + 5counts ) at PF > 0.2 | ± (2% of reading + 10counts ) at PF > 0.2 |
Power (DC) | Range | L | 0.0 W - 120 W | 0.0 W - 240 W | - | - |
H | 100 W - 1300 W | 200 W - 2600 W | 0 W - 5200 W | 0 W - 7800 W |
Resolution | L | 0.1W | - | - |
H | 1W |
Accuracy | L | ± (2% of reading +5counts) |
H | ± (2% of reading +5counts) |
Power Apparent (VA) | Range | L | 0.0VA - 120.0VA | 0.0VA - 240.0VA | - | - |
H | 100VA - 1300VA | 200VA - 2600VA | 0VA - 5200VA | 0VA - 7800VA |
Resolution | L | 0.1VA | - | - |
H | 1VA |
Accuracy | V×A ,Calculated value |
Power Resistive (Q) | Range | L | 0.0VAR~120.0VAR | 0.0VAR~240.0VAR | - | - |
H | 0VAR~1300VAR | 0VAR~2600VAR | 0VAR~5200VAR | 0VAR~7800VAR |
Resolution | L | 0.1VAR | - | - |
H | Bitmap |
Accuracy | ,Calculated value |
Power Factor | Range | 0.000-1.000 |
Resolution | 0.001 |
Accuracy | W/VA, Calculated and displayed to three significant digits |
Crest Factor | Range | 0 to 10.00 |
Resolution | 0.01 |
Accuracy | Apeak / Arms, Calculated and displayed to two significant digits |
GENERAL |
Transient (only for 40 - 70Hz) | Trans-Volt:0.0 - 300.0V, Resolution: 0.1V |
Trans-Site:0.0 - 25.0mS, Resolution: 0.1mS |
Trans-Time:0.5 - 999.9mS, Resolution: 0.1mS |
Trans-Cycle:0 - 9999, 0-Constant |
Inrush Current | 4 times current rating |
Enhanced Over Load Capacity | Over current 110% can hold for 1000 ms without protection |
Operation Key Feature | Soft key, Numeric key, Rotary Knob |
Remote Input Signal (Option) | Test, Reset, Recall program memory 1 through 7 |
Remote Output Signal | Pass, Fail, Test-in-Process |
Calibration | Front Panel Calibration |
Key Lock | Yes, Password Driven |
Synch Output Signal | ON / Event / OFF, Output Signal 5V ,BNC type |
Alarm Volume Setting | Range: 0 - 9; 0=OFF, 1 is softest volume, 9 is loudest volume |
Graphic Display | 240 x 64 dot resolution Monographic LCD / Contrast 9 Levels 1-9 |
Interface (Option) | Ethernet, USB / RS232, GPIB, Linking Card, PLC Remote Input Card |
Protection Circuits | OCP, OVP, OPP, OTP, RCP (Over Current, Over Voltage, Over Power, Over Temp) |
Fan | Temperature Control |
Rear Output | Terminal Block (L,N, G, Ls, Ns) |
Rack mount Handles | Yes |
PFC | PF≥ 0.97 at Full load |
Effieciency | ≥75% (at Full load) | ≥80% (at Full load) |
Auto loop cycle | 0=Continuous, OFF, 2~9999 |
Over Current Fold Back | On/Off , Setting On when output current over setting Hi-A value it will fold back output voltage to keep constant output current is setting Hi-A value |
CE Mark | Yes |
Parallel Output for 1Ø Output | Yes |
Linking Output for 3Ø Output | Yes |
Operation Environment | 0 - 40ºC / 20 - 80% RH |
Dimension, mm*2 | W | 430 | 430 | 430 | 430 |
H | 133.5 (148) | 133.5 (148) | 267 (281) | 400.5 (473) |
D | 530 | 530 | 530 | 530 |
Net Weight | 20Kg | 21Kg | 40Kg | 53Kg |
*1 At working voltage 110V / 220V |
*2 Figure in parentheses are maximum values | *product specifications are subject to change without notice |